ANNEXSupplementary provisions
Materials to be considered as reaction to fire Classes A provided for in Decision 94/611/EC without the need for testing General notes Products should be made only from one or more of the following materials if they are to be considered as Classes A without testing. Products made by gluing one or more of the following materials together will be considered Classes A without testing provided that the glue does not exceed 0,1 % by weight or volume (whichever is the lower). Panel products (e.g. of insulating material) with one or more organic layers, or products containing organic material which is not homogeneously distributed (with the exception of glue) are excluded from the list. Products made by coating one of the following materials with an inorganic layer (e.g. coated metal products) may also be considered as Classes A without testing. None of the materials in the table is allowed to contain more than 1,0 % by weight or volume (whichever is the lower) of homogeneously distributed organic material. >TABLE>