My bookmarksSign up free

Commission Regulation (EU) 2016/1447 ANNEX VI

Commission Regulation (EU) 2016/1447 ANNEX VI

ANNEX VISupplementary provisions

ANNEX VI Frequency ranges and time periods referred to in Article 39(2)(a) Frequency range Time period for operation 47,0 Hz-47,5 Hz 20 seconds 47,5 Hz-49,0 Hz 90 minutes 49,0 Hz-51,0 Hz Unlimited 51,0 Hz-51,5 Hz 90 minutes 51,5 Hz-52,0 Hz 15 minutes Table 8 : Minimum time periods for the 50 Hz nominal system for which a PPM shall be capable of operating for different frequencies deviating from a nominal value without disconnecting from the network.

Read the full instrument →

Other provisions in Commission Regulation (EU) 2016/1447

Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗ · Data as of 2026-07-04

CitationANNEX VI of Commission Regulation (EU) 2016/1447 (LawPlayer, data as of 2026-07-04)

© European Union, https://eur-lex.europa.eu, 1998-2026. Reuse authorised under Commission Decision 2011/833/EU, provided the source is acknowledged.