My bookmarksSign up free

Commission Regulation (EU) 2016/1447 Article 12

Commission Regulation (EU) 2016/1447 Article 12

Rate-of-change-of-frequency withstand capability

Article 12

An HVDC system shall be capable of staying connected to the network and operable if the network frequency changes at a rate between – 2,5 and + 2,5 Hz/s (measured at any point in time as an average of the rate of change of frequency for the previous 1 s).

Read the full instrument → · Read this in context: CHAPTER 1 — Requirements for active power control and frequency support →

Other provisions in CHAPTER 1 — Requirements for active power control and frequency support

Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗ · Data as of 2026-07-04

CitationArticle 12 of Commission Regulation (EU) 2016/1447 (LawPlayer, data as of 2026-07-04)

© European Union, https://eur-lex.europa.eu, 1998-2026. Reuse authorised under Commission Decision 2011/833/EU, provided the source is acknowledged.