Commission Regulation (EU) 2016/1447 Article 32

Network characteristics

Article 32

1.   The relevant system operator shall specify and make publicly available the method and the pre-fault and post-fault conditions for the calculation of at least the minimum and maximum short circuit power at the connection points. 2.   The HVDC system shall be capable of operating within the range of short circuit power and network characteristics specified by the relevant system operator. 3.   Each relevant system operator shall provide the HVDC system owner with network equivalents describing the behaviour of the network at the connection point, enabling the HVDC system owners to design their system with regard to at least, but not limited to, harmonics and dynamic stability over the lifetime of the HVDC system.