ANNEX IISupplementary provisions
ANNEX II Voltage ranges referred to in Article 27: Table 1 Voltage ranges at the connection point between 110 kV and 300 kV Synchronous area Voltage range Continental Europe 0,90 pu-1,118 pu Nordic 0,90 pu-1,05 pu Great Britain 0,90 pu-1,10 pu Ireland and Northern Ireland 0,90 pu-1,118 pu Baltic 0,90 pu-1,118 pu Table 2 Voltage ranges at the connection point between 300 kV and 400 kV Synchronous area Voltage range Continental Europe 0,90 pu-1,05 pu Nordic 0,90 pu-1,05 pu Great Britain 0,90 pu-1,05 pu Ireland and Northern Ireland 0,90 pu-1,05 pu Baltic 0,90 pu-1,097 pu