Commission Regulation (EU) 2017/1485 Article 22

Commission Regulation (EU) 2017/1485 Article 22

Categories of remedial actions

Article 22

1.   Each TSO shall use the following categories of remedial actions: (a) modify the duration of a planned outage or return to service transmission system elements to achieve the operational availability of those transmission system elements; (b) actively impact power flows by means of: (i) tap changes of the power transformers; (ii) tap changes of the phase-shifting transformers; (iii) modifying topologies; (c) control voltage and manage reactive power by means of: (i) tap changes of the power transformers; (ii) switching of the capacitors and reactors; (iii) switching of the power-electronics-based devices used for voltage and reactive power management; (iv) instructing transmission-connected DSOs and significant grid users to block automatic voltage and reactive power control of transformers or to activate on their facilities the remedial actions set out in points (i) to (iii) if voltage deterioration jeopardises operational security or threatens to lead to a voltage collapse in a transmission system; (v) requesting the change of reactive power output or voltage setpoint of the transmission-connected synchronous power generating modules; (vi) requesting the change of reactive power output of the converters of transmission-connected non-synchronous power generating modules; (d) re-calculate day-ahead and intraday cross-zonal capacities in accordance with Regulation (EU) 2015/1222; (e) redispatch transmission or distribution-connected system users within the TSO's control area, between two or more TSOs; (f) countertrade between two or more bidding zones; (g) adjust active power flows through HVDC systems; (h) activate frequency deviation management procedures; (i) curtail, pursuant to Article 16(2) of Regulation (EC) No 714/2009, the already allocated cross-zonal capacity in an emergency situation where using that capacity endangers operational security, all TSOs at a given interconnector agree to such adjustment, and re-dispatching or countertrading is not possible; and (j) where applicable, include the normal or alert state, manually controlled load-shedding. 2.   Where necessary and justified in order to maintain operational security, each TSO may prepare and activate additional remedial actions. The TSO shall report and justify those instances to the relevant regulatory authority and, where applicable, the Member State, at least once every year, after the activation of the additional remedial actions. The relevant reports and justifications shall also be published. The European Commission or the Agency may request the relevant regulatory authority to provide additional information concerning the activation of additional remedial actions in those instances where they affect a neighbouring transmission system.

Read the full instrument → · Read this in context: CHAPTER 1 — System states, remedial actions and operational security limits →

Other provisions in CHAPTER 1 — System states, remedial actions and operational security limits

Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗ · Data as of 2026-07-04

CitationArticle 22 of Commission Regulation (EU) 2017/1485 (LawPlayer, data as of 2026-07-04)

© European Union, https://eur-lex.europa.eu, 1998-2026. Reuse authorised under Commission Decision 2011/833/EU, provided the source is acknowledged.

What to look at next