Commission Regulation (EU) 2017/1485 Article 50

Commission Regulation (EU) 2017/1485 Article 50

Real-time data exchange

Article 50

1.   Unless otherwise provided by the TSO, each power generating facility owner of a power generating module which is a SGU in accordance with Article 2(1)(a) and (e) connected to the distribution system shall provide the TSO and the DSO to which it has the connection point, in real-time, at least the following data: (a) status of the switching devices and circuit breakers at the connection point; and (b) active and reactive power flows, current, and voltage at the connection point. 2.   Each TSO shall define in coordination with the responsible DSOs which SGUs may be exempted from providing the real-time data listed in paragraph 1 directly to the TSO. In such cases, the responsible TSOs and DSOs shall agree on the aggregated real-time data of the SGUs concerned to be delivered to the TSO.