Quality control for grid models
Article 71
When defining the quality controls in accordance with Articles 67(1)(b) and 70(1)(c), all TSOs shall jointly determine controls aimed at least to check: (a) the coherence of the connection status of interconnectors; (b) that voltage values are within the usual operational values for those transmission system elements having influence on other control areas; (c) the coherence of transitory admissible overloads of interconnectors; and (d) that active power and reactive power injections or withdrawals are compatible with usual operational values.