Regulation (EU) 2024/573 Article 6

Regulation (EU) 2024/573 Article 6

Leakage detection systems

Article 6

1.   Operators of stationary equipment listed in Article 5(2), points (a) to (d), that contains fluorinated greenhouse gases listed in Annex I in quantities of 500 tonnes of CO 2 equivalent or more or 100 kilograms or more of gases listed in Section 1 of Annex II, shall ensure that the equipment has a leakage detection system which alerts the operator or a service company of any leakage. 2.   Operators of stationary equipment listed in Article 5(2), points (e) and (f), that contains fluorinated greenhouse gases listed in Annex I in quantities of 500 tonnes of CO 2 equivalent or more and installed from 1 January 2017, shall ensure that the equipment has a leakage detection system which alerts the operator or a service company of any leakage. 3.   Operators of stationary equipment listed in Article 5(2), points (a) to (e), that is subject to paragraphs 1 or 2 of this Article shall ensure that leakage detection systems are checked at least once every 12 months to ensure their proper functioning. 4.   Operators of stationary equipment listed in Article 5(2), point (f), that is subject to paragraph 2 of this Article shall ensure that leakage detection systems are checked at least once every 6 years to ensure their proper functioning.

Read the full instrument → · Read this in context: CHAPTER II — Containment →

Other provisions in CHAPTER II — Containment

Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗ · Data as of 2026-07-04

CitationArticle 6 of Regulation (EU) 2024/573 (LawPlayer, data as of 2026-07-04)

© European Union, https://eur-lex.europa.eu, 1998-2026. Reuse authorised under Commission Decision 2011/833/EU, provided the source is acknowledged.

What to look at next