Commission Regulation (EU) 2016/1447 Article 41

Commission Regulation (EU) 2016/1447 Article 41

Control requirements

Article 41

1.   During the synchronisation of a DC-connected power park module to the AC collection network, the DC-connected power park module shall have the capability to limit any voltage changes to a steady-state level specified by the relevant system operator, in coordination with the relevant TSO. The level specified shall not exceed 5 per cent of the pre-synchronisation voltage. The relevant system operator, in coordination with the relevant TSO, shall specify the maximum magnitude, duration and measurement window of the voltage transients. 2.   The DC-connected power park module owner shall provide output signals as specified by the relevant system operator, in coordination with the relevant TSO.