Commission Regulation (EU) 2016/1447 Article 42

Commission Regulation (EU) 2016/1447 Article 42

Network characteristics

Article 42

With regard to the network characteristics, the following shall apply for the DC-connected power park modules: (a) each relevant system operator shall specify and make publicly available the method and the pre-fault and post-fault conditions for the calculation of minimum and maximum short circuit power at the HVDC interface point; (b) the DC-connected power park module shall be capable of stable operation within the minimum to maximum range of short circuit power and network characteristics of the HVDC interface point specified by the relevant system operator, in coordination with the relevant TSO; (c) each relevant system operator and HVDC system owner shall provide the DC-connected power park module owner with network equivalents representing the system, enabling the DC-connected power park module owners to design their system with regard to harmonics;

Read the full instrument → · Read this in context: CHAPTER 1 — Requirements for DC-connected power park modules →

Other provisions in CHAPTER 1 — Requirements for DC-connected power park modules

Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗ · Data as of 2026-07-04

CitationArticle 42 of Commission Regulation (EU) 2016/1447 (LawPlayer, data as of 2026-07-04)