Commission Regulation (EU) No 548/2014 of 21 May 2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers

Commission Regulation (EU) No 548/2014 of 21 May 2014 on implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to small, medium and large power transformers

Regulation (EU) No 548/2014 · Regulation · 12 articles

Data as of 2026-07-04 · Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗

Subject matter and scope

Article 1

1.   This Regulation establishes ecodesign requirements for placing on the market or putting into service power transformers with a minimum power rating of 1 kVA used in 50 Hz electricity transmission and distribution networks or for industrial applications. The Regulation is only applicable to transformers purchased after the entry into force of the Regulation. 2.   This Regulation shall not apply to transformers specifically designed and used for the following applications: — instrument transformers, specifically designed to supply measuring instruments, meters, relays and other similar apparatus, — transformers with low-voltage windings specifically designed for use with rectifiers to provide a DC supply, — transformers specifically designed to be directly connected to a furnace, — transformers specifically designed for offshore applications and floating offshore applications, — transformers specially designed for emergency installations, — transformers and auto-transformers specifically designed for railway feeding systems, — earthing or grounding transformers, this is, three-phase transformers intended to provide a neutral point for system grounding purposes, — traction transformers mounted on rolling stock, this is, transformers connected to an AC or DC contact line, directly or through a converter, used in fixed installations of railway applications, — starting transformers, specifically designed for starting three-phase induction motors so as to eliminate supply voltage dips, — testing transformers, specifically designed to be used in a circuit to produce a specific voltage or current for the purpose of testing electrical equipment, — welding transformers, specifically designed for use in arc welding equipment or resistance welding equipment, — transformers specifically designed for explosion-proof and underground mining applications  ( 2 ) , — transformers specifically designed for deep water (submerged) applications, — medium Voltage (MV) to Medium Voltage (MV) interface transformers up to 5 MVA, — large power transformers where it is demonstrated that for a particular application, technically feasible alternatives are not available to meet the minimum efficiency requirements set out by this Regulation, — large power transformers which are like for like replacements in the same physical location/installation for existing large power transformers, where this replacement cannot be achieved without entailing disproportionate costs associated to their transportation and/or installation, except as regards the product information requirements and technical documentation set out in Annex I, points 3 and 4.

Definitions

Article 2

For the purpose of this Regulation and its annexes the following definitions shall apply. (1) ‘Power transformer’ means a static piece of apparatus with two or more windings which, by electromagnetic induction, transforms a system of alternating voltage and current into another system of alternating voltage and current usually of different values and at the same frequency for the purpose of transmitting electrical power. (2) ‘Small power transformer’ means a power transformer with a highest voltage for equipment not exceeding 1,1 kV. (3) ‘Medium power transformer’ means a power transformer with a highest voltage for equipment higher than 1,1 kV, but not exceeding 36 kV and a rated power equal to or higher than 5 kVA but lower than 40 MVA. (4) ‘Large power transformer’ means a power transformer with a highest voltage for equipment exceeding 36 kV and a rated power equal or higher than 5 kVA, or a rated power equal to or higher than 40 MVA regardless of the highest voltage for equipment. (5) ‘Liquid-immersed transformer’ means a power transformer in which the magnetic circuit and windings are immersed in liquid. (6) ‘Dry-type transformer’ means a power transformer in which the magnetic circuit and windings are not immersed in an insulating liquid. (7) ‘Medium power pole mounted transformer’ means a power transformer with a rated power of up to 315 kVA suitable for outdoor service and designed to be mounted on the support structures of overhead power lines. (8) ‘Voltage Regulation Distribution Transformer’ means a medium power transformer equipped with additional components, inside or outside of the transformer tank, to automatically control the input or output voltage of the transformer for on-load voltage regulation purposes. (9) ‘Winding’ refers to the assembly of turns forming an electrical circuit associated with one of the voltages assigned to the transformer. (10) ‘Rated voltage of a winding’ (U r ) is the voltage assigned to be applied, or developed at no-load, between the terminals of an untapped winding, or of a tapped winding connected on the principal tapping. (11) ‘High-voltage winding’ refers to the winding having the highest rated voltage. (12) ‘Highest voltage for equipment’ (U m ) applicable to a transformer winding is the highest r.m.s phase-to-phase voltage in a three-phase system for which a transformer winding is designed in respect of its insulation. (13) ‘Rated power’ (S r ) is a conventional value of apparent power assigned to a winding which, together with the rated voltage of the winding, determines its rated current. (14) ‘Load loss’ (P k ) means the absorbed active power at rated frequency and reference temperature associated with a pair of windings when the rated current (tapping current) is flowing through the line terminal(s) of one of the windings and the terminals of the other windings are in short-circuit with any winding fitted with tappings connected to its principal tapping, while further windings, if existing, are open-circuited. (15) ‘No load loss’ (P o ) means the active power absorbed at rated frequency when the transformer is energised and the secondary circuit is open. The applied voltage is the rated voltage, and if the energized winding is fitted with a tapping, it is connected to its principal tapping. (16) ‘Peak Efficiency Index’ (PEI) means the maximum value of the ratio of the transmitted apparent power of a transformer minus the electrical losses to the transmitted apparent power of the transformer.

Eco-design requirements

Article 3

Small power transformers, medium power transformers and large power transformer shall meet the ecodesign requirements set out in Annex I.

Conformity Assessment

Article 4

Conformity assessment shall be carried out applying the internal design control procedure set out in Annex IV to Directive 2009/125/EC or the management system procedure set out in Annex V to that Directive.

Verification procedure for market surveillance purposes

Article 5

When performing the market surveillance checks referred to in Directive 2009/125/EC, Article 3(2), Member State authorities shall apply the verification procedure set out in Annex III to this Regulation.

Indicative Benchmarks

Article 6

The indicative benchmarks for the best-performing transformers technologically possible at the time of adoption of this Regulation are identified in Annex IV.

Review

Article 7

No later than three years after the entry into force, the Commission shall review this Regulation in the light of technological progress and present the results of this review to the Consultation Forum. Specifically, the review will assess, at least, the following issues: — the possibility to set out minimum values of the Peak Efficiency Index for all medium power transformers, including those with a rated power below 3 150 kVA, — the possibility to separate the losses associated to the core transformer from those associated with other components performing voltage regulation functions, where this is the case, — the appropriateness of establishing minimum performance requirements for single-phase power transformers, as well as for small power transformers, — whether concessions made for pole-mounted transformers and for special combinations of winding voltages for medium power transformers are still appropriate, — the possibility of covering environmental impacts other than energy in the use phase.

Entry into force

Article 8

The Regulation shall enter into force on the 20 th day following its publication in the Official Journal of the European Union .

Supplementary provisions

Ecodesign requirements

ANNEX ISupplementary provisions

ANNEX I Ecodesign requirements 1.    Minimum energy performance or efficiency requirements for medium power transformers Medium power transformers shall comply with the maximum allowed load and no-load losses or the Peak Efficiency Index (PEI) values set out in Tables I.1 to I.5, excluding medium power pole-mounted transformers, which shall comply with the maximum allowed load and no load losses values set out in Table I.6. 1.1.    Requirements for three-phase medium power transformers with rated power ≤ 3 150 kVA Table I.1: Maximum load and no-load losses (in W) for three-phase liquid-immersed medium power transformers with one winding with U m ≤ 24 kV and the other one with U m ≤ 1,1 kV   Tier 1 (from 1 July 2015) Tier 2 (from 1 July 2021) Rated Power (kVA) Maximum load losses P k (W)  ( *1 ) Maximum no-load losses P o (W)  ( *1 ) Maximum load losses P k (W)  ( *1 ) Maximum no-load losses P o (W)  ( *1 ) ≤ 25 C k (900) A o (70) A k (600) A o – 10 % (63) 50 C k (1 100 ) A o (90) A k (750) A o – 10 % (81) 100 C k (1 750 ) A o (145) A k (1 250 ) A o – 10 % (130) 160 C k (2 350 ) A o (210) A k (1 750 ) A o – 10 % (189) 250 C k (3 250 ) A o (300) A k (2 350 ) A o – 10 % (270) 315 C k (3 900 ) A o (360) A k (2 800 ) A o – 10 % (324) 400 C k (4 600 ) A o (430) A k (3 250 ) A o – 10 % (387) 500 C k (5 500 ) A o (510) A k (3 900 ) A o – 10 % (459) 630 C k (6 500 ) A o (600) A k (4 600 ) A o – 10 % (540) 800 C k (8 400 ) A o (650) A k (6 000 ) A o – 10 % (585) 1 000 C k (10 500 ) A o (770) A k (7 600 ) A o – 10 % (693) 1 250 B k (11 000 ) A o (950) A k (9 500 ) A o – 10 % (855) 1 600 B k (14 000 ) A o (1 200 ) A k (12 000 ) A o – 10 % (1080 ) 2 000 B k (18 000 ) A o (1 450 ) A k (15 000 ) A o – 10 % (1 305 ) 2 500 B k (22 000 ) A o (1 750 ) A k (18 500 ) A o – 10 % (1 575 ) 3 150 B k (27 500 ) A o (2 200 ) A k (23 000 ) A o – 10 % (1 980 ) Table I.2: Maximum load and no-load losses (in W) for three –phase dry-type medium power transformers with one winding with U m ≤ 24 kV and the other one with U m ≤ 1,1 kV.   Tier 1 (1 July 2015) Tier 2 (1 July 2021) Rated Power (kVA) Maximum load losses P k (W)  ( *2 ) Maximum no-load losses P o (W)  ( *2 ) Maximum load losses P k (W)  ( *2 ) Maximum no-load losses P o (W)  ( *2 ) ≤ 50 B k (1 700 ) A o (200) A k (1 500 ) A o – 10 % (180) 100 B k (2 050 ) A o (280) A k (1 800 ) A o – 10 % (252) 160 B k (2 900 ) A o (400) A k (2 600 ) A o – 10 % (360) 250 B k (3 800 ) A o (520) A k (3 400 ) A o – 10 % (468) 400 B k (5 500 ) A o (750) A k (4 500 ) A o – 10 % (675) 630 B k (7 600 ) A o (1 100 ) A k (7 100 ) A o – 10 % (990) 800 A k (8 000 ) A o (1 300 ) A k (8 000 ) A o – 10 % (1 170 ) 1 000 A k (9 000 ) A o (1 550 ) A k (9 000 ) A o – 10 % (1 395 ) 1 250 A k (11 000 ) A o (1 800 ) A k (11 000 ) A o – 10 % (1 620 ) 1 600 A k (13 000 ) A o (2 200 ) A k (13 000 ) A o – 10 % (1 980 ) 2 000 A k (16 000 ) A o (2 600 ) A k (16 000 ) A o – 10 % (2 340 ) 2 500 A k (19 000 ) A o (3 100 ) A k (19 000 ) A o – 10 % (2 790 ) 3 150 A k (22 000 ) A o (3 800 ) A k (22 000 ) A o – 10 % (3 420 ) Table I.3: Correction of load and no load losses in case of other combinations of winding voltages or dual voltage in one or both windings (rated power ≤ 3 150  kVA) One winding with U m ≤ 24 kV and the other with U m > 1,1 kV The maximum allowable losses in Tables I.1 and I.2 shall be increased by 10 % for no load losses and by 10 % for load losses One winding with U m  = 36 kV and the other with U m ≤ 1,1 kV The maximum allowable losses in Tables I.1 and I.2 shall be increased by 15 % for no load losses and by 10 % for load losses One winding with U m  = 36 kV and the other with U m > 1,1 kV The maximum allowable losses indicated in Tables I.1 and I.2 shall be increased by 20 % for no load losses and by 15 % for load losses Case of dual voltage on one winding In case of transformers with one high-voltage winding and two voltages available from a tapped low-voltage winding, losses shall be calculated based on the higher voltage of the low-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and 1.2. The maximum available power on the lower voltage of the low-voltage winding on such transformers shall be limited to 0,85 of the rated power assigned to the low-voltage winding at its higher voltage. In case of transformers with one low-voltage winding with two voltages available from a tapped high-voltage winding, losses shall be calculated based on the higher voltage of the high-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and I.2., The maximum available power on the lower voltage of the high-voltage winding on such transformer shall be limited to 0,85 of the rated power assigned to the high-voltage winding at its higher voltage. If the full nominal power is available regardless of the combination of voltages, the levels of losses indicated in Tables I.1 and I.2 can be increased by 15 % for no load losses and by 10 % for load losses. Case of dual voltage on both windings The maximum allowable losses in Tables I.1 and I.2 can be increased by 20 % for no load losses and by 20 % for load losses for transformers with dual voltage on both windings. The level of losses is given for the highest possible rated power and on the basis that the rated power is the same regardless of the combination of voltages. 1.2.    Requirements for medium power transformers with rated power > 3 150 kVA Table I.4: Minimum Peak Efficiency Index (PEI) values for liquid immersed medium power transformers Rated Power (kVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) 3 150 < S r ≤ 4 000 99,465 99,532 5 000 99,483 99,548 6 300 99,510 99,571 8 000 99,535 99,593 10 000 99,560 99,615 12 500 99,588 99,640 16 000 99,615 99,663 20 000 99,639 99,684 25 000 99,657 99,700 31 500 99,671 99,712 40 000 99,684 99,724 Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.4 shall be calculated by linear interpolation. Table I.5: Minimum Peak Efficiency Index (PEI) values for dry type medium power transformers Rated Power (kVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) 3 150 < S r ≤ 4 000 99,348 99,382 5 000 99,354 99,387 6 300 99,356 99,389 8 000 99,357 99,390 ≥ 10 000 99,357 99,390 Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.5 shall be calculated by linear interpolation. 1.3.    Requirements for medium power transformers with rated power ≤ 3 150 kVA equipped with tapping connections suitable for operation while being energised or on-load for voltage adaptation purposes. Voltage Regulation Distribution Transformers are included in this category. The maximum allowable levels of losses set out in Tables I.1 and I.2 shall be increased by 20 % for no load losses and 5 % for load losses in Tier 1 and by 10 % for no load losses in Tier 2. 1.4.    Requirements for medium power pole-mounted transformers The levels of load and no load losses indicated in Tables I.1 and I.2 are not applicable to liquid immersed pole-mounted transformers with power ratings between 25 kVA and 315 kVA. For these specific models of medium power pole-mounted transformers, the maximum levels of allowable losses are set out in Table I.6. Table I.6: Maximum load and no-load losses (in W) for medium power liquid immersed pole-mounted transformers   Tier 1 (1 July 2015) Tier 2 (1 July 2021) Rated Power (kVA) Maximum load losses (in W)  ( *3 ) Maximum no-load losses (in W)  ( *3 ) Maximum load losses (in W)  ( *3 ) Maximum no-load losses (in W)  ( *3 ) 25 C k (900) A o (70) B k (725) A o (70) 50 C k (1 100 ) A o (90) B k (875) A o (90) 100 C k (1 750 ) A o (145) B k (1 475 ) A o (145) 160 C k + 32 % (3 102 ) C o (300) C k + 32 % (3 102 ) C o – 10 % (270) 200 C k (2 750 ) C o (356) B k (2 333 ) B o (310) 250 C k (3 250 ) C o (425) B k (2 750 ) B o (360) 315 C k (3 900 ) C o (520) B k (3 250 ) B o (440) 2.    Minimum energy efficiency requirements for large power transformers The minimum efficiency requirements for large power transformers are set out in Tables I.7 and I.8. Table I.7: Minimum Peak Efficiency Index requirements for liquid immersed large power transformers Rated Power (MVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) ≤ 4 99,465 99,532 5 99,483 99,548 6,3 99,510 99,571 8 99,535 99,593 10 99,560 99,615 12,5 99,588 99,640 16 99,615 99,663 20 99,639 99,684 25 99,657 99,700 31,5 99,671 99,712 40 99,684 99,724 50 99,696 99,734 63 99,709 99,745 80 99,723 99,758 ≥ 100 99,737 99,770 Minimum PEI values for MVA ratings that fall in between the ratings given in Table I.7 shall be calculated by linear interpolation. Table I.8: Minimum Peak Efficiency Index requirements for dry-type large power transformers Rated Power (MVA) Tier 1 (1 July 2015) Tier 2 (1 July 2021) Minimum Peak Efficiency Index (%) ≤ 4 99,158 99,225 5 99,200 99,265 6,3 99,242 99,303 8 99,298 99,356 10 99,330 99,385 12,5 99,370 99,422 16 99,416 99,464 20 99,468 99,513 25 99,521 99,564 31,5 99,551 99,592 40 99,567 99,607 50 99,585 99,623 ≥ 63 99,590 99,626 Minimum PEI values for MVA ratings that fall in between the ratings given in Table I.8 shall be calculated by linear interpolation. 3.    Product information requirements From 1 July 2015, the following product information requirements for transformers included in the scope of this Regulation (Article 1) shall be included in any related product documentation, including free access websites of manufacturers: (a) information on rated power, load loss and no-load loss and the electrical power of any cooling system required at no load; (b) for medium power (where applicable) and large power transformers, the value of the Peak Efficiency Index and the power at which it occurs; (c) for dual voltage transformers, the maximum rated power at the lower voltage, according to Table I.3; (d) information on the weight of all the main components of a power transformer (including at least the conductor, the nature of the conductor and the core material); (e) For medium power pole mounted transformers, a visible display ‘For pole-mounted operation only’. The information under a); c) and d) shall also be included on the rating plate of the power transformers. 4.    Technical documentation The following information shall be included in the technical documentation of power transformers: (a) manufacturer's name and address; (b) model identifier, the alphanumeric code to distinguish one model from other models of the same manufacturer; (c) the information required under point 3. If (parts of) the technical documentation is based upon (parts of) the technical documentation of another model, the model identifier of that model shall be provided and the technical documentation shall provide the details of how the information is derived from the technical documentation of the other model, e.g. on calculations or extrapolations, including the tests undertaken by the manufacturer to verify the calculations or extrapolations undertaken. ( *1 )   Maximum losses for kVA ratings that fall in between the ratings given in Table I.1 shall be obtained by linear interpolation. ( *2 )   Maximum losses for kVA ratings that fall in between the ratings given in Table I.2 shall be obtained by linear interpolation. ( *3 )   Maximum allowable losses for kVA ratings that fall in between the ratings given in Table I.6 shall be obtained by linear interpolation.

Measurement and calculation methods

ANNEX IISupplementary provisions

ANNEX II Measurement and calculation methods Measurement method For the purpose of compliance with the requirements of this Regulation, measurements shall be made using a reliable, accurate and reproducible measurement procedure, which takes into account the generally recognised state of the art measurement methods, including methods set out in documents the reference numbers of which have been published for that purpose in the Official Journal of the European Union . Calculation methods The methodology for calculating the Peak Efficiency Index (PEI) for medium and large power transformers is based on the ratio of the transmitted apparent power of a transformer minus the electrical losses to the transmitted apparent power of the transformer. Where:   P 0 is the no load losses measure at rated voltage and rated frequency, on the rated tap   P c0 is the electrical power required by the cooling system for no load operation   P k is the measured load loss at rated current and rated frequency on the rated tap corrected to the reference temperature   S r is the rated power of the transformer or autotransformer on which P k is based

Verification procedure

ANNEX IIISupplementary provisions

ANNEX III Verification procedure When performing the market surveillance checks referred to in Article 3(2) of Directive 2009/125/EC, the authorities of the Member States shall apply the following verification procedure for the requirements set out in Annex I. (1) Member States authorities shall test one single unit per model; (2) The model shall be considered to comply with the applicable requirements set out in Annex I of this Regulation if the values in the technical documentation comply with the requirements set out in Annex I, and if the measured parameters meet the requirements set out in Annex I within the verification tolerances indicated in the Table of this Annex; (3) If the results referred to in point 2 are not achieved, the model shall be considered not to comply with this Regulation. The Member States authorities shall provide all relevant information, including the test results if applicable, to the authorities of the other Member States and the Commission within one month of the decision being taken on the non-compliance of the model. Member States authorities shall use the measurement methods and calculation methods set out in Annex II. Given the weight and size limitations in the transportation of medium and large power transformers, Member States authorities may decide to undertake the verification procedure at the premises of manufacturers, before they are put into service in their final destination. The verification tolerances set out in this Annex relate only to the verification of the measured parameters by Member States authorities and shall not be used by the manufacturer or importer as an allowed tolerance to establish the values in the technical documentation. Table Measured parameter Verification tolerances Load losses The measured value shall not be greater than the declared value by more than 5 %. No load losses The measured value shall not be greater than the declared value by more than 5 %. The electrical power required by the cooling system for no load operation The measured value shall not be greater than the declared value by more than 5 %.

Indicative Benchmarks

ANNEX IVSupplementary provisions

ANNEX IV Indicative Benchmarks At the time of adoption of this Regulation, the best available technology on the market for medium power transformers was identified as follows: (a) Liquid-immersed medium power transformers: A o – 20 %, A k – 20 % (b) Dry-type medium power transformers: A o – 20 %, A k – 20 % (c) Medium power transformers with amorphous steel core: A o – 50 %, A k – 50 % The availability of material to manufacture transformers with amorphous steel core needs further development, before such values of losses can be considered to become minimum requirements in the future.

Other acts of the same type
Commission Regulation (EU) 2015/1185 of 24 April 2015 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for solid fuel local space heaters (Text with EEA relevance)Commission Delegated Regulation (EU) 2015/1186 of 24 April 2015 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to the energy labelling of local space heaters (Text with EEA relevance)Commission Regulation (EU) 2015/639 of 23 April 2015 amending Annex III to Regulation (EC) No 1333/2008 of the European Parliament and of the Council as regards the use of silicon dioxide (E 551) in polyvinyl alcohol-polyethylene glycol-graft-co-polymer (E 1209) (Text with EEA relevance)Commission Regulation (EU) 2015/640 of 23 April 2015 on additional airworthiness specifications for a given type of operations and amending Regulation (EU) No 965/2012Commission Implementing Regulation (EU) 2015/676 of 23 April 2015 concerning the classification of certain goods in the Combined NomenclatureCommission Implementing Regulation (EU) 2015/677 of 23 April 2015 concerning the classification of certain goods in the Combined NomenclatureCommission Delegated Regulation (EU) 2015/1829 of 23 April 2015 supplementing Regulation (EU) No 1144/2014 of the European Parliament and of the Council on information provision and promotion measures concerning agricultural products implemented in the internal market and in third countriesCommission Regulation (EU) 2015/628 of 22 April 2015 amending Annex XVII to Regulation (EC) No 1907/2006 of the European Parliament and of the Council on the Registration, Evaluation, Authorisation and Restriction of Chemicals (‘REACH’) as regards lead and its compounds (Text with EEA relevance)Commission Implementing Regulation (EU) 2015/629 of 22 April 2015 entering a name in the register of protected designations of origin and protected geographical indications (Finocchiona (PGI))Commission Implementing Regulation (EU) 2015/630 of 22 April 2015 amending Implementing Regulation (EU) No 498/2012 on the allocation of tariff-rate quotas applying to exports of wood from the Russian Federation to the European UnionCommission Implementing Regulation (EU) 2015/638 of 22 April 2015 amending Regulation (EC) No 1484/95 as regards fixing representative prices in the poultrymeat and egg sectors and for egg albuminCommission Delegated Regulation (EU) 2015/1342 of 22 April 2015 amending the methodology for the classification of products by activity given in Annex A to Regulation (EU) No 549/2013 of the European Parliament and of the Council (Text with EEA relevance)