ANNEX I
Ecodesign requirements
1. Minimum energy performance or efficiency requirements for medium power transformers
Medium power transformers shall comply with the maximum allowed load and no-load losses or the Peak Efficiency Index (PEI) values set out in Tables I.1 to I.5, excluding medium power pole-mounted transformers, which shall comply with the maximum allowed load and no load losses values set out in Table I.6.
1.1. Requirements for three-phase medium power transformers with rated power ≤ 3 150 kVA
Table I.1: Maximum load and no-load losses (in W) for three-phase liquid-immersed medium power transformers with one winding with U m ≤ 24 kV and the other one with U m ≤ 1,1 kV
Tier 1 (from 1 July 2015)
Tier 2 (from 1 July 2021)
Rated Power (kVA)
Maximum load losses P k (W) ( *1 )
Maximum no-load losses P o (W) ( *1 )
Maximum load losses P k (W) ( *1 )
Maximum no-load losses P o (W) ( *1 )
≤ 25
C k (900)
A o (70)
A k (600)
A o – 10 % (63)
50
C k (1 100 )
A o (90)
A k (750)
A o – 10 % (81)
100
C k (1 750 )
A o (145)
A k (1 250 )
A o – 10 % (130)
160
C k (2 350 )
A o (210)
A k (1 750 )
A o – 10 % (189)
250
C k (3 250 )
A o (300)
A k (2 350 )
A o – 10 % (270)
315
C k (3 900 )
A o (360)
A k (2 800 )
A o – 10 % (324)
400
C k (4 600 )
A o (430)
A k (3 250 )
A o – 10 % (387)
500
C k (5 500 )
A o (510)
A k (3 900 )
A o – 10 % (459)
630
C k (6 500 )
A o (600)
A k (4 600 )
A o – 10 % (540)
800
C k (8 400 )
A o (650)
A k (6 000 )
A o – 10 % (585)
1 000
C k (10 500 )
A o (770)
A k (7 600 )
A o – 10 % (693)
1 250
B k (11 000 )
A o (950)
A k (9 500 )
A o – 10 % (855)
1 600
B k (14 000 )
A o (1 200 )
A k (12 000 )
A o – 10 % (1080 )
2 000
B k (18 000 )
A o (1 450 )
A k (15 000 )
A o – 10 % (1 305 )
2 500
B k (22 000 )
A o (1 750 )
A k (18 500 )
A o – 10 % (1 575 )
3 150
B k (27 500 )
A o (2 200 )
A k (23 000 )
A o – 10 % (1 980 )
Table I.2: Maximum load and no-load losses (in W) for three –phase dry-type medium power transformers with one winding with U m ≤ 24 kV and the other one with U m ≤ 1,1 kV.
Tier 1 (1 July 2015)
Tier 2 (1 July 2021)
Rated Power (kVA)
Maximum load losses P k (W) ( *2 )
Maximum no-load losses P o (W) ( *2 )
Maximum load losses P k (W) ( *2 )
Maximum no-load losses P o (W) ( *2 )
≤ 50
B k (1 700 )
A o (200)
A k (1 500 )
A o – 10 % (180)
100
B k (2 050 )
A o (280)
A k (1 800 )
A o – 10 % (252)
160
B k (2 900 )
A o (400)
A k (2 600 )
A o – 10 % (360)
250
B k (3 800 )
A o (520)
A k (3 400 )
A o – 10 % (468)
400
B k (5 500 )
A o (750)
A k (4 500 )
A o – 10 % (675)
630
B k (7 600 )
A o (1 100 )
A k (7 100 )
A o – 10 % (990)
800
A k (8 000 )
A o (1 300 )
A k (8 000 )
A o – 10 % (1 170 )
1 000
A k (9 000 )
A o (1 550 )
A k (9 000 )
A o – 10 % (1 395 )
1 250
A k (11 000 )
A o (1 800 )
A k (11 000 )
A o – 10 % (1 620 )
1 600
A k (13 000 )
A o (2 200 )
A k (13 000 )
A o – 10 % (1 980 )
2 000
A k (16 000 )
A o (2 600 )
A k (16 000 )
A o – 10 % (2 340 )
2 500
A k (19 000 )
A o (3 100 )
A k (19 000 )
A o – 10 % (2 790 )
3 150
A k (22 000 )
A o (3 800 )
A k (22 000 )
A o – 10 % (3 420 )
Table I.3: Correction of load and no load losses in case of other combinations of winding voltages or dual voltage in one or both windings (rated power ≤ 3 150 kVA)
One winding with U m ≤ 24 kV and the other with U m > 1,1 kV
The maximum allowable losses in Tables I.1 and I.2 shall be increased by 10 % for no load losses and by 10 % for load losses
One winding with U m = 36 kV and the other with U m ≤ 1,1 kV
The maximum allowable losses in Tables I.1 and I.2 shall be increased by 15 % for no load losses and by 10 % for load losses
One winding with U m = 36 kV and the other with U m > 1,1 kV
The maximum allowable losses indicated in Tables I.1 and I.2 shall be increased by 20 % for no load losses and by 15 % for load losses
Case of dual voltage on one winding
In case of transformers with one high-voltage winding and two voltages available from a tapped low-voltage winding, losses shall be calculated based on the higher voltage of the low-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and 1.2. The maximum available power on the lower voltage of the low-voltage winding on such transformers shall be limited to 0,85 of the rated power assigned to the low-voltage winding at its higher voltage.
In case of transformers with one low-voltage winding with two voltages available from a tapped high-voltage winding, losses shall be calculated based on the higher voltage of the high-voltage winding and shall be in compliance with the maximum allowable losses in Tables I.1 and I.2., The maximum available power on the lower voltage of the high-voltage winding on such transformer shall be limited to 0,85 of the rated power assigned to the high-voltage winding at its higher voltage.
If the full nominal power is available regardless of the combination of voltages, the levels of losses indicated in Tables I.1 and I.2 can be increased by 15 % for no load losses and by 10 % for load losses.
Case of dual voltage on both windings
The maximum allowable losses in Tables I.1 and I.2 can be increased by 20 % for no load losses and by 20 % for load losses for transformers with dual voltage on both windings. The level of losses is given for the highest possible rated power and on the basis that the rated power is the same regardless of the combination of voltages.
1.2. Requirements for medium power transformers with rated power > 3 150 kVA
Table I.4: Minimum Peak Efficiency Index (PEI) values for liquid immersed medium power transformers
Rated Power (kVA)
Tier 1 (1 July 2015)
Tier 2 (1 July 2021)
Minimum Peak Efficiency Index (%)
3 150 < S r ≤ 4 000
99,465
99,532
5 000
99,483
99,548
6 300
99,510
99,571
8 000
99,535
99,593
10 000
99,560
99,615
12 500
99,588
99,640
16 000
99,615
99,663
20 000
99,639
99,684
25 000
99,657
99,700
31 500
99,671
99,712
40 000
99,684
99,724
Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.4 shall be calculated by linear interpolation.
Table I.5: Minimum Peak Efficiency Index (PEI) values for dry type medium power transformers
Rated Power (kVA)
Tier 1 (1 July 2015)
Tier 2 (1 July 2021)
Minimum Peak Efficiency Index (%)
3 150 < S r ≤ 4 000
99,348
99,382
5 000
99,354
99,387
6 300
99,356
99,389
8 000
99,357
99,390
≥ 10 000
99,357
99,390
Minimum PEI values for kVA ratings that fall in between the ratings given in Table I.5 shall be calculated by linear interpolation.
1.3. Requirements for medium power transformers with rated power ≤ 3 150 kVA equipped with tapping connections suitable for operation while being energised or on-load for voltage adaptation purposes. Voltage Regulation Distribution Transformers are included in this category.
The maximum allowable levels of losses set out in Tables I.1 and I.2 shall be increased by 20 % for no load losses and 5 % for load losses in Tier 1 and by 10 % for no load losses in Tier 2.
1.4. Requirements for medium power pole-mounted transformers
The levels of load and no load losses indicated in Tables I.1 and I.2 are not applicable to liquid immersed pole-mounted transformers with power ratings between 25 kVA and 315 kVA. For these specific models of medium power pole-mounted transformers, the maximum levels of allowable losses are set out in Table I.6.
Table I.6: Maximum load and no-load losses (in W) for medium power liquid immersed pole-mounted transformers
Tier 1 (1 July 2015)
Tier 2 (1 July 2021)
Rated Power (kVA)
Maximum load losses (in W) ( *3 )
Maximum no-load losses (in W) ( *3 )
Maximum load losses (in W) ( *3 )
Maximum no-load losses (in W) ( *3 )
25
C k (900)
A o (70)
B k (725)
A o (70)
50
C k (1 100 )
A o (90)
B k (875)
A o (90)
100
C k (1 750 )
A o (145)
B k (1 475 )
A o (145)
160
C k + 32 % (3 102 )
C o (300)
C k + 32 % (3 102 )
C o – 10 % (270)
200
C k (2 750 )
C o (356)
B k (2 333 )
B o (310)
250
C k (3 250 )
C o (425)
B k (2 750 )
B o (360)
315
C k (3 900 )
C o (520)
B k (3 250 )
B o (440)
2. Minimum energy efficiency requirements for large power transformers
The minimum efficiency requirements for large power transformers are set out in Tables I.7 and I.8.
Table I.7: Minimum Peak Efficiency Index requirements for liquid immersed large power transformers
Rated Power (MVA)
Tier 1 (1 July 2015)
Tier 2 (1 July 2021)
Minimum Peak Efficiency Index (%)
≤ 4
99,465
99,532
5
99,483
99,548
6,3
99,510
99,571
8
99,535
99,593
10
99,560
99,615
12,5
99,588
99,640
16
99,615
99,663
20
99,639
99,684
25
99,657
99,700
31,5
99,671
99,712
40
99,684
99,724
50
99,696
99,734
63
99,709
99,745
80
99,723
99,758
≥ 100
99,737
99,770
Minimum PEI values for MVA ratings that fall in between the ratings given in Table I.7 shall be calculated by linear interpolation.
Table I.8: Minimum Peak Efficiency Index requirements for dry-type large power transformers
Rated Power (MVA)
Tier 1 (1 July 2015)
Tier 2 (1 July 2021)
Minimum Peak Efficiency Index (%)
≤ 4
99,158
99,225
5
99,200
99,265
6,3
99,242
99,303
8
99,298
99,356
10
99,330
99,385
12,5
99,370
99,422
16
99,416
99,464
20
99,468
99,513
25
99,521
99,564
31,5
99,551
99,592
40
99,567
99,607
50
99,585
99,623
≥ 63
99,590
99,626
Minimum PEI values for MVA ratings that fall in between the ratings given in Table I.8 shall be calculated by linear interpolation.
3. Product information requirements
From 1 July 2015, the following product information requirements for transformers included in the scope of this Regulation (Article 1) shall be included in any related product documentation, including free access websites of manufacturers:
(a)
information on rated power, load loss and no-load loss and the electrical power of any cooling system required at no load;
(b)
for medium power (where applicable) and large power transformers, the value of the Peak Efficiency Index and the power at which it occurs;
(c)
for dual voltage transformers, the maximum rated power at the lower voltage, according to Table I.3;
(d)
information on the weight of all the main components of a power transformer (including at least the conductor, the nature of the conductor and the core material);
(e)
For medium power pole mounted transformers, a visible display ‘For pole-mounted operation only’.
The information under a); c) and d) shall also be included on the rating plate of the power transformers.
4. Technical documentation
The following information shall be included in the technical documentation of power transformers:
(a)
manufacturer's name and address;
(b)
model identifier, the alphanumeric code to distinguish one model from other models of the same manufacturer;
(c)
the information required under point 3.
If (parts of) the technical documentation is based upon (parts of) the technical documentation of another model, the model identifier of that model shall be provided and the technical documentation shall provide the details of how the information is derived from the technical documentation of the other model, e.g. on calculations or extrapolations, including the tests undertaken by the manufacturer to verify the calculations or extrapolations undertaken.
( *1 ) Maximum losses for kVA ratings that fall in between the ratings given in Table I.1 shall be obtained by linear interpolation.
( *2 ) Maximum losses for kVA ratings that fall in between the ratings given in Table I.2 shall be obtained by linear interpolation.
( *3 ) Maximum allowable losses for kVA ratings that fall in between the ratings given in Table I.6 shall be obtained by linear interpolation.