Commission Delegated Regulation (EU) 2016/364 of 1 July 2015 on the classification of the reaction to fire performance of construction products pursuant to Regulation (EU) No 305/2011 of the European Parliament and of the Council (Text with EEA relevance)

Commission Delegated Regulation (EU) 2016/364 of 1 July 2015 on the classification of the reaction to fire performance of construction products pursuant to Regulation (EU) No 305/2011 of the European Parliament and of the Council (Text with EEA relevance)

Delegated Regulation (EU) 2016/364 · Regulation · 4 articles

Data as of 2026-07-04 · Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗

Article 1

Open ↗

When the intended use of a construction product is such that the product may contribute to the generation and spread of fire and smoke within the room or area of origin or beyond, the performance of the product in relation to its reaction to fire shall be classified in accordance with the classification system set out in the Annex.

Article 2

Open ↗

Decision 2000/147/EC is repealed. References to the repealed Decision shall be construed as references to this Regulation.

Article 3

Open ↗

This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union .

Supplementary provisions

ANNEXSupplementary provisions

Open ↗

ANNEX Classes of reaction to fire performance 1.1. For the purposes of Tables 1 to 4 the following symbols  ( 1 ) apply: (1)    ‘ΔΤ’ — temperature rise; (2)    ‘Δm’ — mass loss; (3)    ‘t f ’ — duration of flaming; (4)    ‘PCS’ — gross calorific potential; (5)    ‘LFS’ — lateral flame spread; (6)    ‘SMOGRA’ — smoke growth rate. 1.2. For the purposes of Tables 1, 2 and 3 the following symbols  ( 1 ) apply: (1)    ‘FIGRA’ — fire growth rate; (2)    ‘THR’ — total heat release; (3)    ‘TSP’ — total smoke production; (4)    ‘Fs’ — flame spread. 1.3. For the purposes of Table 4 the following symbols and test parameters apply: (1)    ‘HRR sm30 , kW’ — heat release rate averaged by a 30-s sliding average; (2)    ‘SPR sm60 , m 2 /s’ — smoke production rate averaged by a 60-s sliding average; (3)    ‘Peak HRR, kW’ — maximum of HRR sm30 between test start and end of test, excluded contribution from ignition source; (4)    ‘Peak SPR, m 2 /s’ — maximum of SPR sm60 between test start and end of test; (5)    ‘THR 1200 , MJ’ — total heat release (HRR sm30 ) from test start until end of test, excluded contribution from ignition source; (6)    ‘TSP 1200 , m 2 ’ — total smoke production (HRR sm60 ) from test start until end of test; (7)    ‘FIGRA, W/s’ — fire growth rate index defined as the highest value of the quotient between HRR sm30 excluding the contribution of ignition source and time. Threshold values HRR sm30  = 3 kW and THR = 0,4 MJ; (8)    ‘FS’ — flame spread (damaged length); (9)    ‘H’ — flame spread. 2. For the purposes of Tables 1 to 4 the following definitions apply: (1) ‘material’ means a single basic substance or uniformly dispersed mixture of substances; (2) ‘homogeneous product’ means a product consisting of a single material, having uniform density and composition throughout the product; (3) ‘non-homogeneous product’ means a product that does not satisfy the requirements of a homogeneous product and that is composed of one or more components, substantial and/or non-substantial; (4) ‘substantial component’ means a material that constitutes a significant part of a non-homogeneous product; a layer with a mass per unit area ≥ 1,0 kg/m 2 or a thickness ≥ 1,0 mm is considered to be a substantial component; (5) ‘non-substantial component’ means a material that does not constitute a significant part of a non-homogeneous product; a layer with a mass per unit area < 1,0 kg/m 2 and a thickness < 1,0 mm is considered to be a non-substantial component; (6) ‘internal non-substantial component’ means a non-substantial component that is covered on both sides by at least one substantial component; (7) ‘external non-substantial component’ means a non-substantial component that is not covered on one side by a substantial component. Two or more non-substantial layers that are adjacent to each other, where there are no substantial components in between the layers, shall be considered as one non-substantial component and shall, therefore, be classified in accordance with the criteria for a layer that is a non-substantial component. Table 1 Classes of reaction to fire performance for construction products excluding floorings, linear pipe thermal insulation products, and electric cables Class Test method(s) Classification criteria Additional classification A1 EN ISO 1182  ( 2 ) ; and ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and t f  = 0 (i.e. no sustained flaming)   EN ISO 1716 PCS ≤ 2,0 MJkg – 1  ( 2 ) ; and PCS ≤ 2,0 MJkg – 1  ( 3 )  ( 1 ) ; and PCS ≤ 1,4 MJm – 2  ( 4 ) ; and PCS ≤ 2,0 MJkg – 1  ( 5 )   A2 EN ISO 1182  ( 2 ) ; or ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and t f ≤ 20 s   EN ISO 1716; and PCS ≤ 3,0 MJkg – 1  ( 2 ) ; and PCS ≤ 4,0 MJm – 2  ( 3 ) ; and PCS ≤ 4,0 MJm – 2  ( 4 ) ; and PCS ≤ 3,0 MJkg – 1  ( 5 )   EN 13823 (SBI) FIGRA ≤ 120 Ws – 1 ; and LFS < edge of specimen; and THR 600s ≤ 7,5 MJ Smoke production  ( 6 ) ; and Flaming droplets/particles  ( 7 ) B EN 13823 (SBI); and FIGRA ≤ 120 Ws – 1 ; and LFS < edge of specimen; and THR 600s ≤ 7,5 MJ Smoke production  ( 6 ) ; and Flaming droplets/particles  ( 7 ) EN ISO 11925-2  ( 9 ) : Exposure = 30 s Fs ≤ 150 mm within 60 s C EN 13823 (SBI); and FIGRA ≤ 250 Ws – 1 ; and LFS < edge of specimen; and THR 600s ≤ 15 MJ Smoke production  ( 6 ) ; and Flaming droplets/particles  ( 7 ) EN ISO 11925-2  ( 9 ) : Exposure = 30 s Fs ≤ 150 mm within 60 s D EN 13823 (SBI); and FIGRA ≤ 750 Ws – 1 Smoke production  ( 6 ) ; and Flaming droplets/particles  ( 7 ) EN ISO 11925-2  ( 9 ) : Exposure = 30 s Fs ≤ 150 mm within 60 s E EN ISO 11925-2  ( 9 ) : Exposure = 15 s Fs ≤ 150 mm within 20 s Flaming droplets/particles  ( 8 ) F EN ISO 11925-2  ( 9 ) : Exposure = 15 s Fs > 150 mm within 20 s   Table 2 Classes of reaction to fire performance for floorings Class Test method(s) Classification criteria Additional classification A1 FL EN ISO 1182  ( 10 ) ; and ΔΤ ≤ 30 °C; and Δm ≤ 50 %; and t f  = 0 (i.e. no sustained flaming)   EN ISO 1716 PCS ≤ 2,0 MJkg – 1  ( 10 ) ; and PCS ≤ 2,0 MJkg – 1  ( 11 ) ; and PCS ≤ 1,4 MJm – 2  ( 12 ) ; and PCS ≤ 2,0 MJkg – 1  ( 13 ) A2 FL EN ISO 1182  ( 10 ) ; or ΔΤ ≤ 50 °C; and Δm ≤ 50 %; and t f ≤ 20 s   EN ISO 1716; and PCS ≤ 3,0 MJkg – 1  ( 10 ) ; and PCS ≤ 4,0 MJm – 2  ( 11 ) ; and PCS ≤ 4,0 MJm – 2  ( 12 ) ; and PCS ≤ 3,0 MJkg – 1  ( 13 ) EN ISO 9239-1  ( 14 ) Critical flux  ( 15 ) ≥ 8,0 kWm – 2 Smoke production  ( 16 ) B FL EN ISO 9239-1  ( 14 ) and Critical flux  ( 15 ) ≥ 8,0 kWm – 2 Smoke production  ( 16 ) EN ISO 11925-2  ( 17 ) : Exposure = 15 s Fs ≤ 150 mm within 20 s C FL EN ISO 9239-1  ( 14 ) and Critical flux  ( 15 ) ≥ 4,5 kWm – 2 Smoke production  ( 16 ) EN ISO 11925-2  ( 17 ) : Exposure = 15 s Fs ≤ 150 mm within 20 s D FL EN ISO 9239-1  ( 14 ) and Critical flux  ( 15 ) ≥ 3,0 kWm – 2 Smoke production  ( 16 ) EN ISO 11925-2  ( 17 ) : Exposure = 15 s Fs ≤ 150 mm within 20 s E FL EN ISO 11925-2  ( 17 ) : Exposure = 15 s Fs ≤ 150 mm within 20 s   F FL EN ISO 11925-2  ( 17 ) : Exposure = 15 s Fs > 150 mm within 20 s   Table 3 Classes of reaction to fire performance for linear pipe insulation products Class Test method(s) Classification criteria Additional classification A1 L EN ISO 1182  ( 18 ) ; and ΔT ≤ 30 °C; and Δm ≤ 50 %; and t f  = 0 (i.e. no sustained flaming)   EN ISO 1716 PCS ≤ 2,0 MJkg – 1  ( 18 ) ; and PCS ≤ 2,0 MJkg – 1  ( 19 ) ; and PCS ≤ 1,4 MJm – 2  ( 20 ) ; and PCS ≤ 2,0 MJkg – 1  ( 21 ) A2 L EN ISO 1182  ( 18 ) ; or ΔT ≤ 50 °C; and Δm ≤ 50 %; and t f ≤ 20 s   EN ISO 1716; and PCS ≤ 3,0 MJkg – 1  ( 18 ) ; and PCS ≤ 4,0 MJm – 2  ( 19 ) ; and PCS ≤ 4,0 MJm – 2  ( 20 ) ; and PCS ≤ 3,0 MJkg – 1  ( 21 ) EN 13823 (SBI) FIGRA ≤ 270 Ws – 1 ; and LFS < edge of specimen; and THR 600s ≤ 7,5 MJ Smoke production  ( 22 ) ; and Flaming droplets/particles  ( 23 ) B L EN 13823 (SBI); and FIGRA ≤ 270 Ws – 1 ; and LFS < edge of specimen; and THR 600s ≤ 7,5 MJ Smoke production  ( 22 ) ; and Flaming droplets/particles  ( 23 ) EN ISO 11925-2  ( 25 ) : Exposure = 30 s Fs ≤ 150 mm within 60 s C L EN 13823 (SBI); and FIGRA ≤ 460 Ws – 1 ; and LFS < edge of specimen; and THR 600s ≤ 15 MJ Smoke production  ( 22 ) ; and Flaming droplets/particles  ( 23 ) EN ISO 11925-2  ( 25 ) : Exposure = 30 s Fs ≤ 150 mm within 60 s D L EN 13823 (SBI); and FIGRA ≤ 2 100 Ws – 1 THR 600s ≤ 100 MJ Smoke production  ( 22 ) ; and Flaming droplets/particles  ( 23 ) EN ISO 11925-2  ( 25 ) : Exposure = 30 s Fs ≤ 150 mm within 60 s E L EN ISO 11925-2  ( 25 ) : Exposure = 15 s Fs ≤ 150 mm within 20 s Flaming droplets/particles  ( 24 ) F L EN ISO 11925-2  ( 25 ) : Exposure = 15 s Fs > 150mm within 20 s   Table 4 Classes of reaction to fire performance for electric cables Class Test method(s) Classification criteria Additional classification A ca EN ISO 1716 PCS ≤ 2,0 MJ/kg  ( 26 )   B1 ca EN 50399 (30 kW flame source) and FS ≤ 1,75 m and THR 1200s ≤ 10 MJ and Peak HRR ≤ 20 kW and FIGRA ≤ 120 Ws – 1 Smoke production  ( 27 )  ( 30 ) and Flaming droplets/particles  ( 28 ) and Acidity (pH and conductivity)  ( 29 ) EN 60332-1-2 H ≤ 425 mm B2 ca EN 50399 (20,5 kW flame source) and FS ≤ 1,5 m; and THR 1200s ≤ 15 MJ; and Peak HRR ≤ 30 kW; and FIGRA ≤ 150 Ws – 1 Smoke production  ( 27 )  ( 31 ) and Flaming droplets/particles  ( 28 ) and Acidity (pH and conductivity)  ( 29 ) EN 60332-1-2 H ≤ 425 mm C ca EN 50399 (20,5 kW flame source) and FS ≤ 2,0 m; and THR 1200s ≤ 30 MJ; and Peak HRR ≤ 60 kW; and FIGRA ≤ 300 Ws – 1 Smoke production  ( 27 )  ( 31 ) and Flaming droplets/particles  ( 28 ) and Acidity (pH and conductivity)  ( 29 ) EN 60332-1-2 H ≤ 425 mm D ca EN 50399 (20,5 kW flame source) and THR 1200s ≤ 70 MJ; and Peak HRR ≤ 400 kW; and FIGRA ≤ 1 300 Ws – 1 Smoke production  ( 27 )  ( 31 ) and Flaming droplets/particles  ( 28 ) and Acidity (pH and conductivity)  ( 29 ) EN 60332-1-2 H ≤ 425 mm E ca EN 60332-1-2 H ≤ 425 mm   F ca EN 60332-1-2 H > 425 mm   ( 1 )   The characteristics are defined with respect to the appropriate test method. ( 2 )   For homogeneous products and substantial components of non-homogeneous products. ( 3 )   For any external non-substantial component of non-homogeneous products. ( 1 )    ( 2a ) Alternatively, any external non-substantial component having a PCS ≤ 2,0 MJm – 2 , provided that the product satisfies the following criteria of EN 13823(SBI): FIGRA ≤ 20 Ws – 1 ; and LFS < edge of specimen; and THR 600s ≤ 4,0 MJ; and s1; and d0. ( 4 )   For any internal non-substantial component of non-homogeneous products. ( 5 )   For the product as a whole. ( 6 )    s1 = SMOGRA ≤ 30m 2 s – 2 and TSP 600s ≤ 50m 2 ; s2 = SMOGRA ≤ 180m 2 s – 2 and TSP 600s ≤ 200m 2 ; s3 = not s1 or s2. ( 7 )    d0 = No flaming droplets/particles in EN 13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN 13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification. ( 8 )   No ignition of the paper = no additional classification; Ignition of the paper = d2 classification. ( 9 )   Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack. ( 10 )   For homogeneous products and substantial components of non-homogeneous products. ( 11 )   For any external non-substantial component of non-homogeneous products. ( 12 )   For any internal non-substantial component of non-homogeneous products. ( 13 )   For the product as a whole. ( 14 )   Test duration = 30 minutes. ( 15 )   Critical flux is defined as the radiant flux at which the flame extinguishes or the radiant flux after a test period of 30 minutes, whichever is the lower (i.e. the flux corresponding with the furthest extent of spread of flame). ( 16 )    s1 = Smoke ≤ 750 %.min; s2 = not s1. ( 17 )   Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack. ( 18 )   For homogeneous products and substantial components of non-homogeneous products. ( 19 )   For any external non-substantial component of non-homogeneous products. ( 20 )   For any internal non-substantial component of non-homogeneous products. ( 21 )   For the product as a whole. ( 22 )    s1 = SMOGRA ≤ 105 m 2 s – 2 and TSP 600s ≤ 250 m 2 ; s2 = SMOGRA ≤ 580 m 2 s – 2 and TSP 600s ≤ 1 600 m 2 ; s3 = not s1 or s2. ( 23 )    d0 = No flaming droplets/particles in EN13823 (SBI) within 600s; d1 = No flaming droplets/particles persisting longer than 10s in EN13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification. ( 24 )   No ignition of the paper = no additional classification; Ignition of the paper = d2 classification. ( 25 )   Under conditions of surface flame attack and, if appropriate to the intended use of the product, edge flame attack. ( 26 )   For the product as a whole, excluding metallic materials, and for any external component (i.e. sheath) of the product. ( 27 )    s1 = TSP 1200 ≤ 50 m 2 and Peak SPR ≤ 0,25 m 2 /s s1a = s1 and transmittance in accordance with EN 61034-2 ≥ 80 % s1b = s1 and transmittance in accordance with EN 61034-2 ≥ 60 % < 80 % s2 = TSP 1200 ≤ 400 m 2 and Peak SPR ≤ 1,5 m 2 /s s3 = not s1 or s2 ( 28 )    d0 = No flaming droplets/particles within 1 200 s; d1 = No flaming droplets/particles persisting longer than 10 s within 1 200 s; d2 = not d0 or d1 . ( 29 )   EN 60754-2: a1 = conductivity < 2,5 μS/mm and pH > 4,3; a2 = conductivity < 10 μS/mm and pH > 4,3; a3 = not a1 or a2 . ( 30 )   The smoke class declared for class B1 ca cables must originate from the EN 50399 test (30 kW flame source). ( 31 )   The smoke class declared for class B2 ca , C ca , D ca cables must originate from the EN 50399 test (20,5 kW flame source).

Other acts of the same type
Commission Regulation (EU) 2023/1042 of 26 May 2023 amending Annex II to Regulation (EC) No 396/2005 of the European Parliament and of the Council as regards maximum residue levels for folpet in or on certain products (Text with EEA relevance)Commission Implementing Regulation (EU) 2023/1057 of 26 May 2023 concerning the classification of certain goods in the Combined NomenclatureCommission Implementing Regulation (EU) 2023/1063 of 26 May 2023 entering a name in the register of protected designations of origin and protected geographical indications (‘Suruç Narı’ (PDO))Commission Implementing Regulation (EU) 2023/1064 of 26 May 2023 entering a name in the register of protected designations of origin and protected geographical indications (‘Haricot de Soissons’ (PGI))Council Implementing Regulation (EU) 2023/1027 of 25 May 2023 implementing Regulation (EU) No 36/2012 concerning restrictive measures in view of the situation in SyriaCommission Regulation (EU) 2023/1029 of 25 May 2023 amending Annexes III and V to Regulation (EC) No 396/2005 of the European Parliament and of the Council as regards maximum residue levels for phosmet in or on certain products (Text with EEA relevance)Commission Regulation (EU) 2023/1030 of 25 May 2023 amending Annex IV to Regulation (EC) No 396/2005 of the European Parliament and of the Council as regards Bacillus amyloliquefaciens strain AH2, Bacillus amyloliquefaciens strain IT-45 and Purpureocillium lilacinum strain PL11 (Text with EEA relevance)Commission Implementing Regulation (EU) 2023/1033 of 25 May 2023 amending Implementing Regulation (EU) 2020/1080 imposing a definitive anti-dumping duty on imports of solar glass originating in the People’s Republic of China and Implementing Regulation (EU) 2020/1081 imposing definitive countervailing duties on imports of solar glass originating in the People’s Republic of ChinaRegulation (EU) 2023/1092 of the European Central Bank of 25 May 2023 amending Regulation (EC) No 2157/1999 on the powers of the European Central Bank to impose sanctions (ECB/1999/4) (ECB/2023/13)Commission Delegated Regulation (EU) 2023/1668 of 25 May 2023 supplementing Directive (EU) 2019/2034 of the European Parliament and of the Council with regard to regulatory technical standards specifying the measurement of risks or elements of risks not covered or not sufficiently covered by the own funds requirements set out in Parts Three and Four of Regulation (EU) 2019/2033 of the European Parliament and of the Council and the indicative qualitative metrics for the amounts of additional own funds (Text with EEA relevance)Commission Implementing Regulation (EU) 2023/1020 of 24 May 2023 amending Regulation (EU) No 965/2012 as regards helicopter emergency medical service operations (Text with EEA relevance)Commission Implementing Regulation (EU) 2023/1021 of 24 May 2023 renewing the approval of the active substance Bacillus thuringiensis subsp. kurstaki PB 54 in accordance with Regulation (EC) No 1107/2009 of the European Parliament and of the Council, and amending Commission Implementing Regulation (EU) No 540/2011 (Text with EEA relevance)