Specific ecodesign requirements for RVUs, as referred to in Article 3(1) and 3(3)
ANNEX IISupplementary provisions
ANNEX II Specific ecodesign requirements for RVUs, as referred to in Article 3(1) and 3(3) 1. From 1 January 2016: — SEC, calculated for average climate, shall be no more than 0 kWh/(m 2 .a). — Non-ducted units including ventilation units intended to be equipped with one duct connection on either supply or extract air side shall have a maximum L WA of 45 dB. — All VUs, except dual use units, shall be equipped with a multi-speed drive or variable speed drive. — All BVUs shall have a thermal by-pass facility. 2. From 1 January 2018: — SEC, calculated for average climate, shall be no more than – 20 kWh/(m 2 .a). — Non-ducted units including ventilation units intended to be equipped with one duct connection on either supply or extract air side shall have a maximum L WA of 40 dB. — All VUs, except dual use units, shall be equipped with a multi-speed drive or variable speed drive. — All BVUs shall have a thermal by-pass facility. — Ventilation units with a filter shall be equipped with a visual filter change warning signal.