Commission Regulation (EU) No 1253/2014 ANNEX III

Commission Regulation (EU) No 1253/2014 ANNEX III

Specific ecodesign requirements for NRVUs, as referred to in Article 3(2) and 3(4)

ANNEX IIISupplementary provisions

ANNEX III Specific ecodesign requirements for NRVUs, as referred to in Article 3(2) and 3(4) 1.    From 1 January 2016: — All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive. — All BVUs shall have a HRS. — The HRS shall have a thermal by-pass facility. — The minimum thermal efficiency η t_nrvu of all HRS except run-around HRS in BVUs shall be 67 % and the efficiency bonus E = ( η t_nrvu – 0,67) * 3 000 if the thermal efficiency η t_nrvu is at least 67 %, otherwise E = 0. — The minimum thermal efficiency η t_nrvu of run-around HRS in BVUs shall be 63 % and the efficiency bonus E = ( η t_nrvu – 0,63) * 3 000 if the thermal efficiency η t_nrvu is at least 63 %, otherwise E = 0. — The minimum fan efficiency for UVUs ( ην u ) is — 6,2 % * ln(P) + 35,0 % if P ≤ 30 kW and — 56,1 % if P > 30 kW. — The maximum internal specific fan power of ventilation components ( SFP int_limit ) in W/(m 3 /s) is — for a BVU with run-around HRS — 1 700 + E – 300 * q nom /2 – F if q nom < 2 m 3 /s and — 1 400 + E – F if q nom ≥ 2 m 3 /s; — for a BVU with other HRS — 1 200 + E – 300 * q nom /2 – F if q nom < 2 m 3 /s and — 900 + E – F if q nom ≥ 2 m 3 /s; — 250 for an UVU intended to be used with a filter. 2.    From 1 January 2018: — All ventilation units, except dual use units, shall be equipped with a multi-speed drive or a variable speed drive. All BVUs shall have a HRS. The HRS shall have a thermal by-pass facility. — The minimum thermal efficiency η t_nrvu of all HRS except run-around HRS in BVUs shall be 73 % and the efficiency bonus E = ( η t_nrvu – 0,73) * 3 000 if the thermal efficiency η t_nrvu is at least 73 %, otherwise E = 0. — The minimum thermal efficiency η t_nrvu of run-around HRS in BVUs shall be 68 % and the efficiency bonus E = ( η t_nrvu – 0,68) * 3 000 if the thermal efficiency η t_nrvu is at least 68 %, otherwise E = 0. — The minimum fan efficiency for UVUs ( ην u ) is — 6,2 % * ln(P) + 42,0 % if P ≤ 30 kW and — 63,1 % if P > 30 kW. — The maximum internal specific fan power of ventilation components ( SFP int_limit ) in W/(m 3 /s) is — for a BVU with run-around HRS — 1 600 + E – 300 * q nom /2 – F if q nom < 2 m 3 /s and — 1 300 + E – F if q nom ≥ 2 m 3 /s; — for a BVU with other HRS — 1 100 + E – 300 * q nom /2 – F if q nom < 2 m 3 /s and — 800 + E – F if q nom ≥ 2 m 3 /s; — 230 for an UVU intended to be used with a filter. — If a filter unit is part of the configuration the product shall be equipped with a visual signalling or an alarm in the control system which shall be activated if the filter pressure drop exceeds the maximum allowable final pressure drop.

Read the full instrument →

Other provisions in Commission Regulation (EU) No 1253/2014

Compiled from an official source version. Later amendments or repeals may not be reflected; the official text prevails. · Read the official text ↗ · Data as of 2026-07-04

CitationANNEX III of Commission Regulation (EU) No 1253/2014 (LawPlayer, data as of 2026-07-04)

© European Union, https://eur-lex.europa.eu, 1998-2026. Reuse authorised under Commission Decision 2011/833/EU, provided the source is acknowledged.

What to look at next