Classes of performance in relation to the resistance to fire of construction products, as set out in the Annex, are established.
資料由法律人 LawPlayer整理提供·EU law / curated by LawPlayer from EUR-Lex
Commission Delegated Regulation (EU) 2024/1681 of 6 March 2024 supplementing Regulation (EU) No 305/2011 of the European Parliament and of the Council by establishing classes of performance in relation to the resistance to fire of construction products
Decision 2000/367/EC is repealed.
References to Decision 2000/367/EC shall be construed as references to this Regulation.
This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union .
Schedules & Appendices
ANNEX
A. SYMBOLS
For the purposes of this Annex the following symbols apply:
R
Load-bearing capacity
E
Integrity
I
Insulation
W
Radiation
M
Mechanical action
C
Self-closing
C0-5
Durability of self-closing:
Use category (C)
Number of cycles
5
≥ 200 000
4
≥ 100 000
3
≥ 50 000
2
≥ 10 000
1
≥ 500
0
≥ 1
S
Smoke leakage (in context of ventilation systems)/Smoke control (in context of doors)
P
Continuity of power and signal supply under the standard time temperature curve
PH
Continuity of power and signal supply under constant temperature
G/O
Soot fire resistance
K
Fire protection ability
T
Temperature class expressed in maximum gas temperature in °C (operating temperature)
D
Stability duration under constant temperature
DH
Stability duration under the standard time-temperature curve
F
Functionality of powered smoke and heat ventilators
B
Functionality of natural smoke and heat ventilators
B. CLASSES OF PERFORMANCE IN RELATION TO THE RESISTANCE TO FIRE OF CONSTRUCTION PRODUCTS
General
The relevant definitions, tests and performance criteria are fully described or referenced in the European resistance to fire classification standards, harmonised European product standards, European testing standards, and relevant parts of Eurocodes.
If for asymmetrical elements the declared class of the element is only valid from one side, the class shall be accompanied by this information.
The following classes of performance are expressed in minutes unless otherwise specified.
1. Load-bearing elements without a fire-separating function
Table 1
Applies to
Walls, floors, raised floors, roofs, beams, columns, balconies, walkways, stairs
R
15
20
30
45
60
90
120
180
240
360
2. Load-bearing elements with a fire-separating function
Table 2.1
Applies to
Walls
RE
15
20
30
45
60
90
120
180
240
360
REI
15
20
30
45
60
90
120
180
240
360
REI-M
15
20
30
45
60
90
120
180
240
360
REW
15
20
30
45
60
90
120
180
240
360
Table 2.2
Applies to
Floors, roofs, roof windows, rooflights and shutters
RE
15
20
30
45
60
90
120
180
240
360
REI
15
20
30
45
60
90
120
180
240
360
C
The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test.
Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out.
Table 2.3
Applies to
Raised floors
RE
15
20
30
45
60
90
120
180
240
360
REI
15
20
30
45
60
90
120
180
240
360
Notes
The classification shall be made specific depending on the exposure. The absence of the designation letter ‘r’ refers to standard temperature/time curve exposure (full fire resistance) whereas its presence refers to the constant temperature attack of 500 °C (reduced exposure).
Raised floors satisfying the standard temperature/time curve exposure for a given time are considered to satisfy the reduced exposure conditions for at least the same period.
3. Products and systems for protecting load-bearing elements
Table 3.1
Applies to
Ceilings with no independent fire resistance
Assessment of the contribution to the fire resistance of structural members: Expressed in terms of classification of the load-bearing element being protected.
Notes
If satisfying the criteria with regard to the ‘semi-natural’ fire, the symbol ‘sn’ is added to the classification.
Table 3.2
Applies to
Fire protective coatings (reactive), boards (slabs and mats), renderings (sprays), claddings and screens
Assessment of the contribution to the fire resistance of structural members: Expressed in terms of classification of the load-bearing element being protected.
Notes
For coatings, if satisfying the criteria with regard to the ‘slow heating’ curve, the symbol ‘IncSlow’ is added to the classification.
4. Non-loadbearing elements or products with a fire-separating function
Table 4.1
Applies to
Partitions (including partitions incorporating uninsulated portions) and fixed windows
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
EI-M
15
20
30
45
60
90
120
180
240
360
EW
15
20
30
45
60
90
120
180
240
360
Table 4.2
Applies to
Unloaded roofs
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
EW
15
20
30
45
60
90
120
180
240
360
Table 4.3
Applies to
Cavity barriers
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
Notes
The classification is completed by a separate indication, if satisfying the sudden exposure test for cavity barriers.
Table 4.4
Applies to
Ceilings with independent fire resistance
EI
15
20
30
45
60
90
120
180
240
360
Notes
The classification is completed by indicating how the element has been tested, and refers to a fire from above ‘(a→b)’ or from below ‘(b→a)’ or both ‘(a ↔b)’.
Table 4.5
Applies to
Facades (curtain walls) and external walls (including glazed elements)
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
EW
15
20
30
45
60
90
120
180
240
360
Notes
The classification is completed by ‘(i→o)’; ‘(o→i)’; or ‘(i↔o)’ to indicate whether the element has been tested and fulfils the requirements from the inside only; from the outside only; or from both sides respectively.
The addition of the suffix ‘ef’ indicates that the test was performed on the basis of the external fire curve.
Table 4.6
Applies to
Non-mechanical fire barriers for ventilation ductwork
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
Notes
In addition to meeting the requirements related to integrity (E), the non-mechanical fire barrier shall also:
(a)
be tested from both sides, and
(b)
achieve 360 m 3 /(m 2 h) maximum leakage rate with reference to nominal duct cross-sectional area during the fire test.
There is no S classification for this product, as it has no ambient temperature smoke performance.
‘ve’ and/or ‘ho’ show the product is intended to be used for vertical and/or horizontal use.
Table 4.7
Applies to
Penetration seals
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
Notes
The classification is expressed in terms of classification of the supporting construction with fire-separating function being penetrated.
The classification of pipe penetration seals is completed by the addition of ‘U/U’, ‘C/U’, ‘U/C’, or ‘C/C’ depending on the tested pipe end configuration inside the furnace and outside the furnace respectively (U – uncapped; C – capped).
Table 4.8
Applies to
Combined penetration seals
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
Notes
The classification is expressed in terms of classification of the supporting construction with fire-separating function being penetrated.
The classification shall be completed with the additional relevant classifications of combined elements as given in this annex.
Table 4.9
Applies to
Linear joint seals
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
Notes
The classification is completed by the addition of the symbols
—
‘H’, or ‘V’, or ‘T’ indicating that the classification is valid for the corresponding orientation (Horizontal supporting construction; Vertical supporting construction – vertical joint; Vertical supporting construction – horizontal joint respectively),
—
‘M’, or ‘F’, or ‘B’ indicating the type of splices (Manufactured; Field; or Both manufactured and field respectively),
—
‘X’; or ‘Mxxx’ indicating the movement capability (No movement; or Movement induced (in %) respectively), including the subscript ‘lat’ or ‘shear’ indicating the induced movement, and
—
‘W w1 to w2’ indicating the joint width range (in mm) for which the classification criterion is satisfied (w1 being the lower width and w2 the higher width limit).
Table 4.10
Applies to
Fire resisting doorsets, openable windows (in walls and roofs), openable rooflights and shutters (including those that incorporate glazing, closing devices and other building hardware)
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
EW
15
20
30
45
60
90
120
180
240
360
S 200
For elements and products having passed smoke control criteria depending on test conditions fulfilled.
S a3 or S a4
For elements and products having passed smoke control criteria depending on test conditions fulfilled.
C
The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test.
Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out.
Notes
The EI classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used.
In the case the classification does not cover heating on both the closing and the opening face, this shall be made explicit in the classification.
This table does not include or address products for smoke ventilation.
Additional smoke control classification of large industrial doorsets is possible to a leakage limit of 50 m 3 /h.
Table 4.11
Applies to
Closures for conveyers and track bound transportation systems
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
EW
15
20
30
45
60
90
120
180
240
360
C
The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test.
Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out.
Notes
The EI classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. An EI classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system.
Sustained operational capability of any clearing device and/or any separating device for a conveyor system is identified by using a ‘T’.
Table 4.12
Applies to
Air transfer grilles
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
EW
15
20
30
45
60
90
120
180
240
360
Notes
If satisfying the criteria with regard to integrity during the open state, the symbol ‘resist flame’ is added to the classification.
If satisfying the criteria with regard to the ‘smoldering’ curve, the symbol ‘IncSlow’ is added to the classification.
Table 4.13
Applies to
Service ducts and shafts
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
Notes
The classification defines how the element has been tested and refers to a fire from the inside ‘(i→o)’ or from the outside ‘(o→i)’ or both ‘(i ↔o)’. In addition, the symbols ‘ve’ and/or ‘ho’ show the product is intended to be used for vertical and/or horizontal use.
Table 4.14
Applies to
Chimneys
G + distance in mm (e.g. G 50) or O + distance in mm (e.g. O 50)
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
T (operating temperature) in °C
80
100
120
140
160
200
250
300
400
450
600
Notes
Distance not required for built-in products.
The classification defines how the element has been tested and refers to a fire from the outside ‘(o→i)’ or both ‘(i ↔o)’.
‘ve’ and/or ‘ho’ show the product is intended to be used for vertical and/or horizontal use.
Table 4.15
Applies to
Wall and ceiling coverings
K 1
10
15
20
30
45
60
90
120
180
240
360
K 2
10
15
20
30
45
60
90
120
180
240
360
Notes
The suffixes ‘1’ and ‘2’ indicate which substrates, fire behaviour criteria and extension rules are used in this classification.
5. Products for use in ventilation systems (excluding smoke and heat exhaust ventilation)
Table 5.1
Applies to
Fire resisting ventilation ducts
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
S
10 m 3 /(m 2 h) maximum leakage rate with reference to the duct surface area during the fire test
Notes
In addition to meeting the requirements related to integrity (E) the duct must also achieve 15 m 3 /(m 2 h) maximum leakage rate with reference to duct surface area during the fire test.
The classification defines how the element has been tested and refers to a fire from the inside ‘(i→o)’ or from the outside ‘(o→i)’ or both ‘(i ↔o)’.
‘ve’ and/or ‘ho’ show the product is intended to be used for vertical and/or horizontal use.
The classification shall indicate the pressure difference used in the test.
Table 5.2
Applies to
Fire dampers
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
S
200 m 3 /(m 2 h) maximum leakage rate with reference to nominal duct cross sectional area:
(a)
smallest size at ambient temperature;
(b)
largest size at ambient temperature and during the fire test.
Notes
In addition to meeting the requirements related to integrity (E) the fire damper shall also:
(a)
be tested from both sides, and
(b)
achieve 360 m 3 /(m 2 h) maximum leakage rate with reference to nominal duct cross sectional area during the fire test.
‘ve’ and/or ‘ho’ show the product is intended to be used for vertical (e.g., wall mounted) and/or horizontal (e.g., floor mounted) use.
‘H’ indicates a fire damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a horizontal blade axis or geometry.
‘V’ indicates a fire damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a vertical blade axis or geometry.
6. Products to be used within electrical, power control and communication building service installations
Table 6.1
Applies to
Fire protective systems for cable systems and associated components
P
15
20
30
45
60
90
120
180
240
360
Notes
The classification shall indicate:
The type of cables which can be installed within the fire protective systems, i.e. any standard cable or only specific cables; and
the cables configurations which can be protected and the operating voltage, i.e.:
—
either to all types of power cables (rated voltage 300/500 V) for an operating voltage up to 230/400 V (three-phase AC);
—
either to all types of power cables (rated voltage 450/750 V up to 0,6/1 kV) for an operating voltage up to 400/690 V (Three-phase AC);
—
either to all types of signal-/control cables (rated voltage up to 170 V) for an operating voltage up to 110 V; or
—
any combination of the above possibilities.
Table 6.2
Applies to
Unprotected electric, power control and communication cables with intrinsic fire resistance
P ca
15
20
30
45
60
90
120
180
240
360
Notes
For power cables and control cables the classification shall indicate for which rated voltage the performance criteria are satisfied.
Table 6.3
Applies to
Unprotected small electric, power control and communication cables with intrinsic fire resistance (< 20 mm diameter and with conductor sizes ≤ 2,5 mm 2 )
PH ca
15
20
30
45
60
90
120
180
240
360
Notes
For power cables and control cables the classification shall indicate for which rated voltage the performance criteria are satisfied.
7. Products to be used in smoke and heat control systems
Table 7.1
Applies to
Single compartment smoke control ducts
E 600
15
20
30
45
60
90
120
180
240
360
S
5 m 3 /(m 2 h) maximum leakage rate with reference to duct surface area at ambient temperature and 5 m 3 /(m 2 h) maximum leakage rate related to the duct surface area during the fire test.
Notes
In addition to meeting the requirements related to integrity (E) the duct must also achieve 10 m 3 /(m 2 h) maximum leakage rate with reference to duct surface area during the fire test.
The classification is completed by the suffix ‘single’ for products intended to be used for single compartment use only.
‘ve’ and/or ‘ho’ show the product is intended to be used for vertical and/or horizontal use, within the compartment.
‘500’, ‘1 000 ’, ‘1 500 ’ show the product is intended to be used up to these values of under-pressure, measured in Pa at ambient temperature.
Table 7.2
Applies to
Multi-compartment fire resistant smoke control ducts
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
S
5 m 3 /(m 2 h) maximum leakage rate with reference to duct surface area at ambient temperature and 5 m 3 /(m 2 h) maximum leakage rate related to the duct surface area during the fire test.
Notes
In addition to meeting the requirements related to integrity (E) the duct must also achieve 10 m 3 /(m 2 h) maximum leakage rate with reference to duct surface area during the fire test.
The classification is completed by the suffix ‘multi’ for products intended to be used for multi-compartment use.
‘ve’ and/or ‘ho’ show the product is intended to be used for vertical and/or horizontal use.
‘500’, ‘1 000 ’, ‘1 500 ’ show the product is intended to be used up to these values of under-pressure, measured in Pa at ambient temperature.
Table 7.3
Applies to
Single compartment smoke control dampers
E 600
15
20
30
45
60
90
120
180
240
360
S
200 m 3 /(m 2 h) maximum leakage rate with reference to nominal duct cross sectional area:
(a)
smallest size at ambient temperature;
(b)
largest size at ambient temperature and during the fire test.
Notes
In addition to meeting the requirements related to integrity (E) the single compartment smoke control damper shall also:
(a)
be tested from both sides,
(b)
pass a maintenance of opening test, and
(c)
achieve 360 m 3 /(m 2 h) maximum leakage rate with reference to nominal duct cross sectional area during the fire test
(1)
smallest size at ambient temperature, and
(2)
largest size at ambient temperature and during the fire test.
The classification is completed by the suffix ‘single’ for products intended for single compartment use.
‘ved’, ‘vew’, ‘vedw’ and/or ‘hod’, ‘how’, ‘hodw’ show the product is intended to be used for vertical and/or horizontal use, together with mounting in a duct or in a wall/floor or both respectively.
‘H’ indicates a single compartment smoke control damper capable of satisfying integrity (E) for the classification period having a horizontal blade axis or geometry,
‘V’ indicates a single compartment smoke control damper capable of satisfying integrity (E) for the classification period having a vertical blade axis or geometry.
‘500’, ‘1 000 ’ and ‘1 500 ’ show that the product is intended to be used up to this value of under-pressure in Pa at ambient temperature.
‘AA’ denotes for use with applications providing automatic activation, ‘MA’ denotes for use with applications requiring manual intervention or providing automatic activation.
‘C 300 ’, ‘C 10 000 ’, ‘C MOD ’ or ‘C 300 (N)’, ‘C 10 000 (N)’, ‘C MOD (N)’ show the product is intended to be used in smoke control only systems, fully controlled smoke control systems and smoke control systems combined with environmental systems or modulating smoke control dampers intended to be used in any system having a controlled or variable position, tested under load, or without load (N), respectively.
‘HOT 400/30’ (High Operational Temperature) indicates that the single compartment smoke control damper has been subjected to an additional test to demonstrate that it has the ability to be opened and closed during a period of 30 minutes of temperatures up to 400 °C.
Table 7.4
Applies to
Multi-compartment fire resistant smoke control dampers
E
15
20
30
45
60
90
120
180
240
360
EI
15
20
30
45
60
90
120
180
240
360
S
200 m 3 /(m 2 h) maximum leakage rate with reference to nominal duct cross sectional area:
(a)
smallest size at ambient temperature;
(b)
largest size at ambient temperature and during the fire test.
Notes
In addition to meeting the requirements related to integrity (E) or integrity and insulation (EI) the multi-compartment fire resistant smoke control damper shall also:
(a)
be tested from both sides,
(b)
pass a maintenance of opening test, and
(c)
achieve 360 m 3 /(m 2 h) maximum leakage with reference to nominal duct cross sectional area during the fire test
(1)
smallest size at ambient temperature, and
(2)
largest size at ambient temperature and during the fire test.
The classification is completed by the suffix ‘multi’ for products intended for multi-compartment use.
‘ved’, ‘vew’, ‘vedw’ and/or ‘hod’, ‘how’, ‘hodw’ show the product is intended to be used for vertical and/or horizontal use, together with mounting in a duct or in a wall/floor or both respectively.
‘H’ indicates a multi-compartment fire resistant smoke control damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a horizontal blade axis or geometry,
‘V’ indicates a multi-compartment fire resistant smoke control damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a vertical blade axis or geometry.
‘500’, ‘1 000 ’ and ‘1 500 ’ show that the product is intended to be used up to this value of under-pressure in Pa at ambient temperature.
‘AA’ denotes for use with applications providing automatic activation, ‘MA’ denotes for use with applications requiring manual intervention or providing automatic activation.
‘C 300 ’, ‘C 10 000 ’, ‘C MOD ’ or ‘C 300 (N)’, ‘C 10 000 (N)’, ‘C MOD (N)’ show the product is intended to be used in smoke control only systems, fully controlled smoke control systems and smoke control systems combined with environmental systems or modulating smoke control dampers intended to be used in any system having a controlled or variable position, tested under load, or without load (N), respectively.
‘HOT 400/30’ (High Operational Temperature) indicates that the multi-compartment fire resistant smoke control damper has been subjected to an additional test to demonstrate that it has the ability to be opened and closed during a period of 30 minutes of temperatures up to 400 °C.
Table 7.5
Applies to
Smoke barriers
D 600
15
20
30
45
60
90
120
180
240
360
DH
15
20
30
45
60
90
120
180
240
360
Table 7.6
Applies to
Powered smoke and heat control ventilators (fans), including connectors
F 200
15
20
30
45
60
90
120
180
240
360
F 300
15
20
30
45
60
90
120
180
240
360
F 400
15
20
30
45
60
90
120
180
240
360
F 600
15
20
30
45
60
90
120
180
240
360
F 842
15
20
30
45
60
90
120
180
240
360
Table 7.7
Applies to
Natural smoke and heat exhaust ventilators
B 300
15
20
30
45
60
90
120
180
240
360
B 600
15
20
30
45
60
90
120
180
240
360
Β θ
15
20
30
45
60
90
120
180
240
360
Notes
Where θ indicates the exposure condition (temperature), higher than 300 °C.
These products are designed to open in case of fire and do not have an integrity (E) classification.
Cite this act
Commission Delegated Regulation (EU) 2024/1681 of 6 March 2024 supplementing Regulation (EU) No 305/2011 of the European Parliament and of the Council by establishing classes of performance in relation to the resistance to fire of construction products (EUR-Lex). Retrieved via LawPlayer, https://lawplayer.com/eu/act/32024R1681
© European Union, https://eur-lex.europa.eu, 1998-2026. Reuse authorised under Commission Decision 2011/833/EU, provided the source is acknowledged.
本頁資料來源:EUR-Lex·整理提供:法律人 LawPlayer· lawplayer.com